8KW base station air conditioner
Yibike air-cooled air conditioner specifically designed for computer roomsEUA008
Yibike air-cooled air conditioner specifically designed for
computer rooms
EUA008
skill
art
gauge
lattice
book
Contents
1. Summary
1.1. Notes
1.2 Design standards
1.3 Scope of application
2. Product introduction
Product Introduction
Product Features
3. Technical parameters
4. Main component configuration list
5. Installation Requirements
5.1 Usage Environment
5.2 Outdoor and indoor unit installation requirements
5.3 Specifications for refrigeration connection pipes
5.4 Electrical connection specifications
1. Summary
1.1. Notes
This technical specification is applicable to the air-cooled air conditioning for computer rooms produced by Guangdong Yibike Energy Technology Co., LTD. It aims to regulate the technical parameters, configuration of major components, installation requirements, etc. of the product, and serves as a guide for marketing, technical support and other related work. Guangdong Yibik Energy Technology Co., Ltd. reserves the final right of interpretation of this technical specification. Please confirm with the relevant personnel when using this technical specification specifically.
1.2. Design standards
The main standards followed by the products referred to in this technical specification are as follows:
GB/T19413 "Unitary Air Conditioning Units for Computer and Data Processing Rooms"
GB4706.1 Safety of household and similar electrical appliances - Part 1: General requirements
GB4706.32 Safety for Household and similar electrical appliances Particular requirements for heat pumps, air conditioners and dehumidifiers
GB5226.1 Mechanical and Electrical safety Mechanical and electrical equipment - Part 1: General technical conditions
GB9237 Safety requirements for mechanical refrigeration systems for refrigeration and heating purposes
GB/T17758 "Unit-type Air Conditioning Units"
GB25130 "Safety Requirements for Unitary Air Conditioners"
GB50736 Code for Design of Heating, Ventilation and Air Conditioning in Civil Buildings
GB50243 Code for Acceptance of Construction Quality of Ventilation and Air Conditioning Works
GB50174 Code for Design of Computer Rooms for Electronic Information Systems
1.3. Scope of application
The products referred to in this technical specification are applicable to all kinds of places that require constant temperature and humidity: computer rooms, data centers, program-controlled switch rooms, satellite mobile communication stations, medical equipment rooms, laboratories, precision electronic instrument production workshops, etc.
2. Product Description
Product Introduction
The computer room air conditioner is a special air conditioner designed by Guangdong Yibike Energy Technology Co., Ltd. for IDC computer rooms and communication base stations that operate non-stop 24 hours a day, 365 days a year. The units are stable, safe and reliable, ensuring that the equipment in the computer room operates in the most suitable environment for a long time.
The unit is designed with a frame structure, and all components can be conveniently repaired or replaced from the front and sides of the unit. But to ensure the cooling effect, the side and back of the unit should be more than 400mm away from the wall. Unit air supply mode: Front air supply.
Product features
The unit has control functions for cooling, heating and dehumidification, temperature and humidity can be set, and the system can work according to the set indoor temperature and humidity state. The control of each function is guaranteed within the set control points and precision control range.
Temperature adjustment range: +16 ° C to +40 ° C, temperature adjustment accuracy: 1 ±° C;
Humidity adjustment range: 20% to 95%RH, humidity adjustment accuracy: 5%RH.±
1) Refrigeration
It uses a direct expansion refrigeration cycle, which is highly energy-efficient, reliable and has low operating costs, in line with the "green and environmentally friendly" requirements.
2) Dehumidification
The unit automatically controls the fan speed according to the room requirements, thereby precisely controlling the dehumidification capacity of the unit, which can greatly improve humidity control accuracy while dehumidifying quickly.
3) Reheat (optional)
When the system needs dehumidification, the unit can start the electric heating to compensate for the cooling capacity as required. The unit is equipped with a PTC electric heater and has overheat protection.
4) Humidification (optional)
Use an electrode humidifier to achieve a humidification output of 30% to 100%.
5) Group control
Supports multi-unit networking for centralized control, and also has rotating and backup functions.
6) Remote monitoring
Supports remote monitoring, provides RS485 interface, supports MODBUS protocol. It has three remote functions: remote measurement, remote control, and remote signaling.
7) Alarm protection
Fan failure alarm, electric heater overload alarm, humidifier failure alarm, phase sequence protection alarm, system high/low pressure protection alarm, filter clogging alarm, temperature too high/too low alarm, etc.
8) Other functions
The unit has functions such as manual/automatic operation control, shift and backup, fault self-diagnosis, fault alarm record storage, power loss storage/automatic recovery/power-on auto-start, multi-level password, etc. It can also record the cumulative working time of the compressor, fan, humidifier and heater.
3. Technical parameters
Model Power supply Air supply mode | EUA008A 380V/3PH/50Hz Forward air supply | |
Cooling capacity Total cooling capacity Apparent cooling capacity |
kW kW |
7.5 6.9 |
Indoor fan Number of fans Circulating air volume Fan power |
Taiwan m3/h W | DC fan 2 2800 80 |
Compressor form Compressor quantity | Rotor type 1 | |
Humidification capacity Humidification power | kg/h kW | 3 2.2 |
Electric heater | kW | 3 |
Indoor fan noise | dB(A) | 56 |
External dimensions Width (W) Depth (D) High (H |
mm mm mm |
510 425 1865 |
Weight | kg | 93 |
Takeover Refrigerant piping: exhaust/liquid pipe Condensate drainage Humidifier intake/drain |
mm mm mm |
12.7/9.52 21 19/32 |
Outdoor unit | ||
Quantity | Taiwan | 1 |
Model | ECA012 | |
Heat exchange capacity | kW | 12 |
Rated air volume | m3/h | 3500 |
Number of fans | a | 1 |
Rated power (per fan) | W | 175 |
Dimensions Width (W) Depth (D) High (H) |
mm mm mm |
960 370 810 |
Weight | kg | 34 |
4. Main component configuration list
Serial number | Part Names | Manufacturer, brand | Model | Quantity | place of origin | Notes |
1 | Compressor | Haili | WHP09100ASC | 1 | Shanghai | |
2 | Indoor fan | Kaibang motor + Shunwei fan blades | ZWR40-D55+ Φ 400 | 1 | Zhuhai, Foshan | |
3 | Outdoor fan | Junfeng | 175 | 1 | Foshan | |
4 | Expansion valve | Sanhua | DPF (TS1) 1.8 C - 03 | 1 | Hangzhou | |
5 | Controller | Aliwei | HAC02M3 | 1 | Sichuan | |
6 | Monitor | Aliwei | HAC02D1Z color touch screen | 1 | Sichuan | |
7 | Temperature and humidity sensor | Aliwei | HAC02S1 | 1 | Sichuan | |
8 | Humidifying tank | Huaxia Ruichi | RSD-02 | 1 | Beijing | Optional |
9 | Electric heater | Oriental | PTC 3kW | 1 | Zhejiang | Optional |
10 |
5. Installation requirements
5.1 Usage Environment
Runtime environment Requirements
The operating environment of the unit meets the requirements of GB4798.3 "Environmental Conditions for the Application of Electrical and Electronic Products"
Project | Specific Requirements |
Ambient temperature | Indoor: 16 ° C to 40 ° C Outdoor: -15 ° C to 45 ° C |
Ambient humidity | 20% to 95% RH |
Operating voltage | 380V(±15%)/3 Ph /50Hz |
Protection class | Indoor unit: IPX0, Outdoor unit: IPX4 |
Altitude | Less than 1000m and greater than 1000m will be used with a reduced limit |
Storage environment requirements
The storage environment of the unit meets the requirements of GB4798.1 "Environmental Conditions for the Application of Electrical and Electronic Products - Storage"
Project | Specific Requirements |
Storage environment | Store indoors, clean and free of dust, etc |
Ambient temperature | -20 ° C to 54 ° C |
Ambient humidity | 5% to 95% RH |
Storage time | The total transportation and storage time shall not exceed 6 months. After 6 months, the performance needs to be recalibrated |
5.2 Outdoor and indoor unit installation requirements
l At least 600mm of operating space should be reserved on the front of the indoor unit, and no less than 400mm of operating space should be reserved on both sides and the back.
l Outdoor units can only be installed upright;
l There should be no obstructions within 2 meters directly in front of the outdoor unit's air outlet, 0.3 meters to the left and back, and 0.6 meters to the right to ensure smooth ventilation.
Outdoor unit vertical installation diagram
5.3 Specifications for refrigeration connection pipes
Connection pipe specification and size table (indoor and outdoor connection pipe length within 30 meters) :
Pipe diameter (mm) | Liquid tube diameter (mm) | Condensate drain pipe diameter (mm) |
12.7 | 9.52 | 21 |
Table of installation dimensions for outdoor units higher than indoor units, see Figure 5.1
Parameters | Size requirements |
H | ≤20m |
△H | For every 6m ascent |
Inclination | 1/100 |
The outdoor unit is below the indoor unit installation dimensions table, see Figure 5.2
Parameters | Size requirements |
H | ≤5m |
Inclination | 1/100 |
Figure 5.1 Installation diagram of the outdoor unit above the indoor unit
Figure 5.2 Installation of the outdoor unit below the indoor unit
5.4 Electrical connection specifications
Model | EFA008A(without heating and humidification) | EFA008A(with heating and humidification) |
Maximum current (A) | 7 | 11.5 |
Cord diameter (mm2) | 5 * 2.5 | 5 * 2.5 |
Air switch (A) | 16 | 16 |