8KW base station air conditioner

Price: $0 $0
Stock: 99999

Yibike air-cooled air conditioner specifically designed for computer roomsEUA008

Buy Now Add To Cart

Yibike air-cooled air conditioner specifically designed for
computer rooms

EUA008

 

skill

art

gauge

lattice

book

 

 

 

 

 

 



Contents

1.   Summary  

1.1.   Notes  

1.2   Design standards  

1.3   Scope of application  

2.   Product introduction  

Product Introduction  

Product Features  

3.   Technical parameters  

4.   Main component configuration list  

5.   Installation Requirements  

5.1 Usage Environment  

5.2 Outdoor and indoor unit installation requirements  

5.3 Specifications for refrigeration connection pipes  

5.4 Electrical connection specifications  

 


1. Summary

1.1. Notes

This technical specification is applicable to the air-cooled air conditioning for computer rooms produced by Guangdong Yibike Energy Technology Co., LTD. It aims to regulate the technical parameters, configuration of major components, installation requirements, etc. of the product, and serves as a guide for marketing, technical support and other related work. Guangdong Yibik Energy Technology Co., Ltd. reserves the final right of interpretation of this technical specification. Please confirm with the relevant personnel when using this technical specification specifically.

 

1.2. Design standards

The main standards followed by the products referred to in this technical specification are as follows:

GB/T19413 "Unitary Air Conditioning Units for Computer and Data Processing Rooms"

GB4706.1 Safety of household and similar electrical appliances - Part 1: General requirements

GB4706.32 Safety for Household and similar electrical appliances Particular requirements for heat pumps, air conditioners and dehumidifiers

GB5226.1 Mechanical and Electrical safety Mechanical and electrical equipment - Part 1: General technical conditions

GB9237 Safety requirements for mechanical refrigeration systems for refrigeration and heating purposes

GB/T17758 "Unit-type Air Conditioning Units"

GB25130 "Safety Requirements for Unitary Air Conditioners"

GB50736 Code for Design of Heating, Ventilation and Air Conditioning in Civil Buildings

GB50243 Code for Acceptance of Construction Quality of Ventilation and Air Conditioning Works

GB50174 Code for Design of Computer Rooms for Electronic Information Systems

 

1.3. Scope of application

The products referred to in this technical specification are applicable to all kinds of places that require constant temperature and humidity: computer rooms, data centers, program-controlled switch rooms, satellite mobile communication stations, medical equipment rooms, laboratories, precision electronic instrument production workshops, etc.

 

 

2. Product Description

图片1.jpg

Product Introduction

 

The computer room air conditioner is a special air conditioner designed by Guangdong Yibike Energy Technology Co., Ltd. for IDC computer rooms and communication base stations that operate non-stop 24 hours a day, 365 days a year. The units are stable, safe and reliable, ensuring that the equipment in the computer room operates in the most suitable environment for a long time.

The unit is designed with a frame structure, and all components can be conveniently repaired or replaced from the front and sides of the unit. But to ensure the cooling effect, the side and back of the unit should be more than 400mm away from the wall. Unit air supply mode: Front air supply.

 

Product features

The unit has control functions for cooling, heating and dehumidification, temperature and humidity can be set, and the system can work according to the set indoor temperature and humidity state. The control of each function is guaranteed within the set control points and precision control range.

Temperature adjustment range: +16 ° C to +40 ° C, temperature adjustment accuracy: 1 ±° C;

Humidity adjustment range: 20% to 95%RH, humidity adjustment accuracy: 5%RH.±

 

1) Refrigeration

It uses a direct expansion refrigeration cycle, which is highly energy-efficient, reliable and has low operating costs, in line with the "green and environmentally friendly" requirements.

 

2) Dehumidification

The unit automatically controls the fan speed according to the room requirements, thereby precisely controlling the dehumidification capacity of the unit, which can greatly improve humidity control accuracy while dehumidifying quickly.

 

3) Reheat (optional)

When the system needs dehumidification, the unit can start the electric heating to compensate for the cooling capacity as required. The unit is equipped with a PTC electric heater and has overheat protection.

 

4) Humidification (optional)

Use an electrode humidifier to achieve a humidification output of 30% to 100%.

 

5) Group control

Supports multi-unit networking for centralized control, and also has rotating and backup functions.

 

6) Remote monitoring

Supports remote monitoring, provides RS485 interface, supports MODBUS protocol. It has three remote functions: remote measurement, remote control, and remote signaling.

 

7) Alarm protection

Fan failure alarm, electric heater overload alarm, humidifier failure alarm, phase sequence protection alarm, system high/low pressure protection alarm, filter clogging alarm, temperature too high/too low alarm, etc.

 

8) Other functions

The unit has functions such as manual/automatic operation control, shift and backup, fault self-diagnosis, fault alarm record storage, power loss storage/automatic recovery/power-on auto-start, multi-level password, etc. It can also record the cumulative working time of the compressor, fan, humidifier and heater.

 

 

3. Technical parameters

Model

Power supply

Air supply mode


EUA008A

380V/3PH/50Hz

Forward air supply

Cooling capacity

Total cooling capacity

Apparent cooling capacity

 

kW

kW

 

7.5

6.9

Indoor fan

Number of fans

Circulating air volume

Fan power

 

Taiwan

m3/h

W

DC fan

2

2800

80

Compressor form

Compressor quantity


Rotor type

1

Humidification capacity

Humidification power

kg/h

kW

3

2.2

Electric heater

kW

3

Indoor fan noise

dB(A)

56

External dimensions

Width (W)

Depth (D)

High (H

 

mm

mm

mm

 

510

425

1865

Weight

kg

93

Takeover

Refrigerant piping: exhaust/liquid pipe

Condensate drainage

Humidifier intake/drain

 

mm

mm

mm

 

12.7/9.52

21

19/32

Outdoor unit

Quantity

Taiwan

1

Model


ECA012

Heat exchange capacity

kW

12

Rated air volume

m3/h

3500

Number of fans

a

1

Rated power (per fan)

W

175

Dimensions

Width (W)

Depth (D)

High (H)

 

mm

mm

mm

 

960

370

810

Weight

kg

34

       

 

图片2.png


图片3.png

4. Main component configuration list

Serial number

Part Names

Manufacturer, brand

Model

Quantity

place of origin

Notes

Compressor

Haili

WHP09100ASC

1

Shanghai


Indoor fan

Kaibang motor + Shunwei fan blades

ZWR40-D55+

Φ 400

1

Zhuhai, Foshan


Outdoor fan

Junfeng

175

1

Foshan


Expansion valve

Sanhua

DPF (TS1) 1.8 C - 03

1

Hangzhou


Controller

Aliwei

HAC02M3

1

Sichuan


Monitor

Aliwei

HAC02D1Z color touch screen

1

Sichuan


Temperature and humidity sensor

Aliwei

HAC02S1

1

Sichuan


Humidifying tank

Huaxia Ruichi

RSD-02

1

Beijing

Optional

Electric heater

Oriental

PTC 3kW

1

Zhejiang

Optional

10 







 

 5. Installation requirements

5.1 Usage Environment

Runtime environment Requirements

The operating environment of the unit meets the requirements of GB4798.3 "Environmental Conditions for the Application of Electrical and Electronic Products"

Project

Specific Requirements

Ambient temperature

Indoor: 16 ° C to 40 ° C

Outdoor: -15 ° C to 45 ° C

Ambient humidity

20% to 95% RH

Operating voltage

380V(±15%)/3 Ph /50Hz

Protection class

Indoor unit: IPX0, Outdoor unit: IPX4

Altitude

Less than 1000m and greater than 1000m will be used with a reduced limit


Storage environment requirements

The storage environment of the unit meets the requirements of GB4798.1 "Environmental Conditions for the Application of Electrical and Electronic Products - Storage"

Project

Specific Requirements

Storage environment

Store indoors, clean and free of dust, etc

Ambient temperature

-20 ° C to 54 ° C

Ambient humidity

5% to 95% RH

Storage time

The total transportation and storage time shall not exceed 6 months. After 6 months, the performance needs to be recalibrated

 

图片4.png


5.2 Outdoor and indoor unit installation requirements


图片5.png

 

At least 600mm of operating space should be reserved on the front of the indoor unit, and no less than 400mm of operating space should be reserved on both sides and the back.

Outdoor units can only be installed upright;

There should be no obstructions within 2 meters directly in front of the outdoor unit's air outlet, 0.3 meters to the left and back, and 0.6 meters to the right to ensure smooth ventilation.

 

Outdoor unit vertical installation diagram


 

5.3 Specifications for refrigeration connection pipes

Connection pipe specification and size table (indoor and outdoor connection pipe length within 30 meters) :

Pipe diameter (mm)

Liquid tube diameter (mm)

Condensate drain pipe diameter (mm)

12.7

9.52

21

 

Table of installation dimensions for outdoor units higher than indoor units, see Figure 5.1

Parameters

Size requirements

H

≤20m

△H

For every 6m ascent

Inclination

1/100

 

The outdoor unit is below the indoor unit installation dimensions table, see Figure 5.2

Parameters

Size requirements

H

≤5m

Inclination

1/100

Figure 5.1 Installation diagram of the outdoor unit above the indoor unit

图片6.png

 

 

 

Figure 5.2 Installation of the outdoor unit below the indoor unit

图片7.png

 

5.4 Electrical connection specifications

Model

EFA008A(without heating and humidification)

EFA008A(with heating and humidification)

Maximum current (A)

7

11.5

Cord diameter (mm2)

5 * 2.5

5 * 2.5

Air switch (A)

16

16

 